Conduit Fill Chart

󰊼
Free Android app — works offline, no pop-up ads.
Get it on Google Play
The most THHN / THWN-2 conductors of one size allowed in each EMT trade size, worked out from NEC Chapter 9: conduit areas from Table 4, conductor areas from Table 5, and the fill limits from Table 1 (53% for one conductor, 31% for two, 40% for three or more). Note 7 rounds a count up when its decimal is 0.8 or more. Informative Annex C, Table C.1 lists EMT counts made the same way.
Values are from the 2017 NEC (NFPA 70); check the edition your AHJ enforces. Count the equipment grounding conductor too (Chapter 9 Note 3). This is a reference for same-size stranded conductors only: compact conductors, mixed sizes and nipples are not covered, and the ampacity adjustment for more than three current-carrying conductors (310.15) and local rules still apply.

THHN in EMT, 14 to 6 AWG

Example: 12 AWG THHN in 1/2" EMT. 40% of 0.304 in² is 0.1216 in²; one wire is 0.0133 in², and 0.1216 ÷ 0.0133 = 9.14, so 9.
Most THHN / THWN-2 conductors in EMT, 14 to 6 AWG
EMT size14 AWG12 AWG10 AWG8 AWG6 AWG
1/2"129532
3/4"22161064
1"35261697
1¼"6145281612
1½"8461382216
2"138101633626
2½"2411761116446
3"3642661679669
3½"47634721912691
4"608443279161116

THHN in EMT, 4 AWG to 1/0

Large conductors in small conduit fall back to the 31% limit for two conductors and 53% for one: one 1/0 THHN fits in 1/2" EMT (0.53 × 0.304 ÷ 0.1855 = 0.87, rounded up by Note 7), two do not.
Most THHN / THWN-2 conductors in EMT, 4 AWG to 1/0
EMT size4 AWG3 AWG2 AWG1 AWG1/0 AWG
1/2"11111
3/4"21111
1"43311
1¼"76543
1½"108754
2"16131187
2½"2824201512
3"4336302219
3½"5647402925
4"7160513732
Counts are whole conductors after the Note 7 round-up, which is why a few of them fill a little over the limit (22 × 14 AWG in 3/4" EMT is 40.04%).